Commissioning
Basic settings
Entry of motor data
6
6.5
6.5.4
6.5−5
EDSVS9332P EN 5.0−07/2013
9300std089
Fig. 6.5−6 "Motor adj" menu of the parameter menu
Procedure
1. Open the "Parameter menu ® Motor/Feedback ® Motor adj" menu.
2.
Click on C0086 and select the motor whose data corresponds best with the connected
motor.
Note!
The available motors are listed in chapter "Motor selection list". 6.5−6
3. Click on C0006 and select the motor control operating mode.
4.
Enter the data of the connected motor in the following codes. The data can be found on
the nameplate or the data sheet of the motor.
C0022 Maximum current I
max
of the motor
C0081 Rated motor power
C0084 Stator resistance of the motor
(The setting is only required if the demands on the control characteristics are
very high)
C0085 Leakage inductance of the motor
(The setting is only required if the demands on the control characteristics are
very high)
C0087 Rated motor speed
C0088 Rated motor current
C0089 Rated motor frequency
C0090 Rated motor voltage
C0091 Cos j.
5. Save the setting with C0003 = 1.
For non−Lenze motors or
Lenze motors not listed under
C0086