DC−bus operation
Fuses and cable cross−sections
10
10.3
10.3−2
EDSVS9332P EN 5.0−07/2013
Inverter DC fuse 14 × 51
(EFSGR0xx0AYHx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type Mains Rated current of fuse Rated current of fuse +U
G
, −U
G
Laying system
B2 C
[A] [A] [mm
2
] [mm
2
]
EVS9321
3/PE
400 V
12
12 1.5 1.5
EVS9322
12
12 1.5 1.5
EVS9323
12
12 1.5 1.5
EVS9324
20
20 1.5 1.5
EVS9325
40
40 4.0 4.0
EVS9326
50
50 6.0
1)
4.0
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2
can be connected to
the inverter.
Inverter DC fuse NH1
(EFSGRxxx0ANVx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type Mains Rated current of fuse Rated current of fuse +U
G
, −U
G
Laying system
B2 C
[A] [A] [mm
2
] [mm
2
]
EVS9327
3/PE
400 V
100
100
− 25
EVS9328 100
100
− 25
EVS9329 200
−
− 25
EVS9330 200
−
− 50
EVS9331 200
−
− 50
Inverter DC fuse NH2
(EFSGRxxx0ANWx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type Mains Rated current of fuse Rated current of fuse +U
G
, −U
G
Laying system
B2 C
[A] [A] [mm
2
] [mm
2
]
EVS9332
3/PE
400 V
250 − − 95