Safety instructions
Safety instructions for the installation according to UL
2
2.4
2.4−4
EDSVS9332P EN 5.0−07/2013
ƒ EVS9330  EVS9332:
– Suitable for use on a circuit capable of delivering not more
than 10000 rms symmetrical amperes, 480 V maximum,
when protected by fuses.
– Suitable for use on a circuit capable of delivering not more
than 50000 rms symmetrical amperes, 480 V maximum,
when protected by J, T or R class fuses.
– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.