Lenze EVS9332xP Manual de usuario Pagina 147

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 445
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 146
Wiring of the standard device
Control terminals
Technical data
5
5.8
5.8.7
5.8−11
EDSVS9332P EN 5.0−07/2013
Analog inputs, analog outputs
Terminal Description Field Values
X6/1
X6/2
Analog input 1
Voltage range
Level −10 V ... +10 V
Resolution 5 mV (11 Bit + sign)
Current range
Level −20 mA ... +20 mA
Resolution 20 mA (10 Bit + sign)
X6/3
X6/4
Analog input 2
Voltage range
Level −10 V ... +10 V
Resolution 5 mV (11 Bit + sign)
X6/62 Analog output 1
Level −10 V ... +10 V
Load capacity Maximum 2 mA
Resolution 20 mV (9 bits + sign)
Cycle time 1 ms (smoothing time t = 2 ms)
X6/63 Analog output 2
Level −10 V ... +10 V
Load capacity Maximum 2 mA
Resolution 20 mV (9 bits + sign)
Cycle time 1 ms (smoothing time t = 2 ms)
X6/7 GND1 Reference potential for analog signals
Isolated to X5/39 (GND2)