Wiring of the standard device
Notes on project planning
Motor cable
5
5.2
5.2.10
5.2−9
EDSVS9332P EN 5.0−07/2013
Note!
The cable cross−sections have been assigned to the permissible
current loading of the motor cables under the following
conditions:
ƒ Compliance with IEC/EN 60204−1 for fixed cable installation
ƒ Compliance with IEC 60354−2−52, table A.52−5 when using the
cable in a trailing cable
ƒ Laying system C
ƒ Ambient temperature 45 °C
ƒ Continuous motor operation at a
– standstill current I
0
for servo motors or a
– rated current I
R
for three−phase asynchronous motors
The user is responsible for selecting a motor cable which
complies with the requirements of the current conditions if
different situations arise. Different situations may arise due to:
ƒ Laws, standards, national and regional regulations
ƒ Type of application
ƒ Motor utilisation
ƒ Ambient and operating conditions
ƒ Laying system and bundling of cables
ƒ Cable type
Motor cable
permanently installed for trailing cable Cable cross−section
I
M
[A] I
M
[A] [mm
2
] [AWG]
10.0 11.8 1.0 18
13.8 17.3 1.5 16
19.1 23.7 2.5 14
25.5 30.9 4.0 12
32.8 41.0 6.0 10
45.5 55.5 10 8
60.1 75.5 16 6
76.4 92.8 25 4
94.6 115 35 2
114 140 50 1
146 179 70 00
177 217 95 000
205 252 120 0000
Note!
Information on the design of the motor cable is provided in the
"System cables and system connectors" manual.
Cable cross−section