Wiring of the standard device
Standard devices in the power range 15 ... 30 kW
Mains connection, DC supply
5
5.5
5.5.3
5.5−4
EDSVS9332P EN 5.0−07/2013
PE
+UG -UG
L1 L2
L3
3
01 2
L1, L2, L3
+U , -U
PE
GG
M6
5Nm
44 lb-in
}
+
PE
9300std034
Fig. 5.5−2 Mains connection, DC supply for drive controllers 15 ... 30 kW
PE stud
Connect PE cable with ring cable lug
Conductive surface
Shield clamp
Place shield with large surface on control cabinet mounting plate and fasten
with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud
Mains and DC bus connection
L1, L2, L3: Connection of mains cable with ring cable lugs
+U
G
, −U
G
: Connection of DC−bus components or connection of the controller
in the DC−bus system (see system manual)