Configuration
Monitoring
Monitoring times for process data input objects
8
8.2
8.2.3
8.2−3
EDSVS9332P EN 5.0−07/2013
8.2.3 Monitoring times for process data input objects
Each process data input object can monitor whether a telegram has been
received within a time set. As soon as a telegram arrives, the corresponding
monitoring time (C0357) is restarted ("retriggerable monoflop" function).
The following assignments are valid:
Setting the response to the monitoring:
ƒ C0591 for CAN1_IN ("CE1")
ƒ C0592 for CAN2_IN ("CE2")
ƒ C0593 for CAN3_IN ("CE3")
The following can be set:
ƒ 0 = error (TRIP) − controller sets controller inhibit (CINH)
ƒ 2 = warning
ƒ 3 = monitoring is switched off
You can also use the signals as binary output signals, e. g. for the assignment
of the output terminal.
If the controller disconnects from the CAN bus due to faulty telegrams, the
"BusOffState" (CE4) signal is set.
"BusOffState" can trigger an error (TRIP) or warning (like CE1, CE2, CE3). You
can also switch the signal off. The response is set via C0595. You can also
assign the terminal output.
Changes with regard to the baud rates, the CAN node addresses, or the
addresses of process data objects are only valid after a reset node.
The reset node can be effected by:
ƒ A reconnection of the low−voltage supply
ƒ Reset node via the bus system
ƒ Reset node via C0358
Bus off
Reset node