Installation
8200SHB01994-18
4.1.5.5 Assembly of 821X-C-V003
Note!
With 821X-C-V003, the cooler is screwed to the back of the controller cold plate.
Provide enough free space for the dismantling of the controller.
Control-cabinet assembly of Lenze convection coolers
The fixing screws are included in the delivery package of the convection cooler.
1. Use the 8 fixing screws M5 x 20 to screw the convection cooler onto the
cold plate.
- For other screws observe the insertion depth t into the cold plate:
8mm$ t $ 10 mm
- Tightening torque: 3.4 Nm.
2. Push the gasket over the front onto the convection cooler.
3. Push the controller from behind through the cut-out at the back of the
control cabinet.
4. Screw the fixing screws 8 x M6 x 12 from inside the control cabinet
through the back and the gasket in the tapped holes of the heat sink.
- Tighten screws crosswise.
- Tightening torque: 5.4 Nm.