Configuration
8200SHB01997-8
7.3.2 Change and store parameters with fieldbus modules.
RS232/485 fieldbus module 2102IB
- Parameter setting via the serial LECOM interface is supported by the PC
programs ”Global Drive Control” and ”LEMOC2” (see Accessories).
- The codes of parameters set PAR 1 are set via the LECOM interface by
entering the code number as address. To address the codes of parameter
set PAR 2 it is necessary to add 2000 to the code number.
- Example: Address of minimum field frequency f
dmin
:
In the parameter set PAR1: C011.
INTERBUS fieldbus module 2111IB
The parameter setting for controller with INTERBUS is described in the Operating
Instructions for the 2111IB fieldbus module.
System bus module 2171IB/2172IB
Theparameter setting for controllers with thesystem bus (CAN)is described in the
Operating Instructions for the 2171IB/2172IB system bus module.
7.3.3 Dynamic parameter change
Only “HVAC” controllers
Code Name Possible settings IMPORTANT
Lenze Choice Info
C003¤ Save parameter set -1- -0- Data will not be stored on EEPROM;
all data will be lost when switching
off the mains
-1- Data will be stored on EEPROM;
setting when switching on the
mains
Function Continuous change of parameters is possible via a bus connection module. The EEPROM is not
damaged by exceeding the max. permissible number of write accesses.
Selection
C003 = -0-
- Continuous parameter change is not permitted because the data is not stored on EEPROM.
C003 = -1-
- Changed parameters are immediatelystoredon EEPROM.
Important C003 = -0- isonlyvalid for C010, C011, C012, C013, C037, C038, C105, C181 andC182.
With C003 -1- the continuous change of parameters is not permitted because the max. permissible
write accessesof the EEPROMcanbe exceeded.