Technical Data
8200SHB0199
3-11
150 % overload Type 8221 8222 8223 8224
Order No. EVF8221-E EVF8222-E EVF8223-E EVF8224-E
Variant ”Cold Plate” Type 8221-V003 8222-V003
Order No. EVF8221-C-V003 EVF8222-C-V003
Variant “HVAC” Type 8221-V020 8222-V020 8223-V020 8224-V020
Order No. EVF8221-E-V020 EVF8222-E-V020 EVF8223-E-V020 EVF8224-E-V020
Power derating [%/K]
[%/m]
40 C<T
V
<50C: 2.5 %/K
1000 ma.m.s.l. h$ 4000 ma.m.s.l.: 5 %/1000 m
Field
Resolution Absolute 0.02 Hz
frequency
Digitalsetpoint selection Accuracy á0.05 Hz
Analog setpoint selection
Linearity á0.5 %(max. selectedsignal level: 5 Vor 10 V)
Temperature
sensitivity
0 ¡ 40 C: +0.4 %
Offset á0%
Weight
”Cold Plate” without heat sink
m[kg] 15
11
15
11
15
-
33.5
-
Printed in bold Data for the operation with factorysetting and a chopper frequency of 8 kHz.
1)
This power canbe additionallyobtainedwhen operatinga matchingmotor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Only with variant “HVAC”
5)
Must only be operated with C144 = -1- (automatic chopper frequency derating at J
max
=+5C). Ensure not to
exceedthe currents.
* Chopper frequency of the inverter