Configuration
8200SHB0199
7-45
Only series “HVAC”:
Level inversion The function “Motor potentiometer” can be influenced through level inversion.
Example
C114 = -3-
- Terminals E1 and E2 are level inverted. The function Motor potentiometer” is then activated
according to the following table:
Function
E1 E2
Setpoint = 0 Hz (T
iQSP
, C105)
1)
HIGH HIGH
Reduce setpoint until f
dmin
(T
if
, C013)
2)
LOW HIGH
Increase setpoint untilf
dmax
(T
ir
, C012) HIGH LOW
Setpoint remains constant LOW LOW
1)
HIGHlevel at terminalsE1 and E2 reduce the setpoint via the QSPramp(C105)until
f
d
=0Hz.
2)
Onlypossible, if the setpoint has exceeded f
dmin
before.
Activation of the function Motor potentiometer” via normally-open contacts.
E1 E2 E3 E4 20
C007 = -26-
- The JOG value has priority over the function Motor potentiometer”.