Technical Data
8200SHB0199
3-9
150 % overload Type 8215 8216 8217 8218
Order No. EVF8215-E EVF8216-E EVF8217-E EVF8218-E
Variant ”Cold Plate” Type 8215-V003 8216-V003 8217-V003 8218-V003
Order No. EVF8215-C-V003 EVF8216-C-V003 EVF8217-C-V003 EVF8218-C-V003
Variant “HVAC” Type 8215-V020 8216-V020 8217-V020 8218-V020
Order No. EVF8215-E-V020 EVF8216-E-V020 EVF8217-E-V020 EVF8218-E-V020
Motor voltage
3)
V
M
[V] 0-3xV
mains
/0Hz¡ 50 Hz, if required up to480 Hz
Power loss (operation with I
rx
) P
loss
[W] 150 200 280 400
Power derating [%/K]
[%/m]
40 C<T
V
<50C: 2.5 %/K
1000 ma.m.s.l. h$ 4000 ma.m.s.l.: 5 %/1000 m
Field
Resolution Absolute 0.02 Hz
frequency
Digitalsetpoint selection Accuracy á0.05 Hz
Analog setpoint selection
Linearity á0.5 %(max. selectedsignal level: 5 Vor 10 V)
Temperature
sensitivity
0 ¡ 40 C: +0.4 %
Offset á0%
Weight
”Cold Plate” without heat sink
”Cold Plate” with heat sink
m[kg] 5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
5.3
2.8
20.8
Printed in bold Data for the operation with factorysetting and a chopper frequency of 8 kHz.
1)
This power canbe additionallyobtainedwhen operatinga matchingmotor
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage
4)
Only with variant “HVAC”
* Chopper frequency of the inverter