
Configuration
8200SHB0199
7-11
Function The controllers are equipped with two parameter sets: PAR1 and PAR2. You can switch from one
parameter set to the other during operation. If the second parameter set is activated, for instance,
additionalaccelerationand deceleration times or three additionalJOGfrequenciescanbe activated.
Selection Change to PAR2 via the digital input terminal PAR,
e.g. terminal E3 if C007 = -1- (see table ”Terminal configuration”).
Overwrite parameter sets withfactorysetting.
Copy the parameter sets to different controllers of the same type using the keypad:
- 820X820X
- 821X821X
- 822X/824X822X/824X
Series “HVAC”:
Copy the parameter sets to different controller using the keypad.
Overwrite parameter sets with controller-dependent data (C002 = -7-).
Important
The controller works with PAR1 when using the factory setting.
For copying the data fromthe keypad(C002 = -3-, -4-, -5-):
- Parameters C016, C036, C088, C091, C079 will not be transferred.
SelectC002 = -7- totransferthese parameters (onlyseries“HVAC”).
The LCD displays the activated parameter set only in the code level.
- The codes marked with *in the code table are the same for PAR1 and PAR2.
Comentarios a estos manuales