Lenze 8200 Frequency inverters Manual de usuario Pagina 123

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 311
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 122
Commissioning
8200SHB01995-18
5.5 Application examples for PID controllers
5.5.1 Pump application with pressure control
K14
K12
K11
Ctrl.
enable
Down
JOG
L
M
3~
Frequency inverter 8210/8220/8240
Pressure setpoint
e.g. from PC/PLC/
keypad
Fault message
e.g. PLC
Analog display for
actual pressure
Actual pressure
-
+
p
Pressure sensor
0 ... 10 V, 0/4 ... 20 mA
(external aux. energy/
supply required
Pump
W
K35.0144_gba
V
U
Z1
K1
F1
Z2
L1L2L3
Up
H/RE
28
E1
E3
E2
E4
20
62
7
8
9
X1
2101
W
V
U
G
-U
G
+U
L1
L2
L3
PE
FIG 5-2 Application of a pump with pressure control
Z1 Mains filterrequired for radiointerference level Aor B. For mainschokes see chapter 3.4 ff.
Z2 Motor filter/sine filter required for long motor cables or motors not designed for inverter operation
(see chapter4.2.7.2).
Shield all signal and motor cables. Please observe the corresponding installation instructions in chapters 4.2 and 4.3.
Show/Hide Bookmarks
Vista de pagina 122
1 2 ... 118 119 120 121 122 123 124 125 126 127 128 ... 310 311

Comentarios a estos manuales

Sin comentarios