Technical Data
8200SHB01993-4
3.3 General data/application conditions
Field Values
Vibration resistance Germanischer Lloyd, general conditions
Humidity class Humidityclass F without condensation (average relative humidity85 %)
Permissible temperature
r
a
n
g
During transport of the controller: -25 C¡+70C
P
r
m
i
s
s
i
b
l
t
m
p
r
a
t
u
r
range
During storage of the controller: -25 C¡+55C
During operation of the controller: 0 C¡+40C
+40C¡+50C
without power derating
with power derating
Permissible installation
height
h$ 1000 ma.m.s.l.
1000 ma.m.s.l. h$ 4000 ma.m.s.l.
without power derating
with power derating
Degree of pollution VDE 0110 part 2 pollution degree 2
Noise emission RequirementstoEN50081-2, EN50082-1, IEC 22G-WG4 (Cv)21
Limitvalue class A to EN 55011 (industry) with mains filter
Limit value class B to EN 55022 (residential area)withmains filterandinstallationintocontrol
cabinet
Noise immunity
Limit values maintainedwithmainsfilter
RequirementstoEN50082-2, IEC 22G-WG4 (Cv)21
Requirements Standard Severities
ESD EN61000-4-2 3, i.e. 8 kV with air discharge,
6 kV with contact discharge
RF interference (enclosure) EN61000-4-3 3, i.e. 10 V/m; 27¡1000 MHz
Burst EN61000-4-4 3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
IEC 1000-4-5 3, i.e. 1.2/50 ³s,
1 kV phase-phase,
2 kV phase-PE
Insulation strength Overvoltage categoryIIItoVDE0110
Packaging to DIN 4180 Types 820X, 821X, 824X
Types 822X,
821X/2X/4XHVAC (V020)
Dust packaging
Transport packaging
Enclosure
Types 82XX, 82XXHVAC (V020) IP20
NEMA 1: Protectionagainst contact
Types 8215 - 8218, 822X, 824X,
8215/16/17/18/2X/4XHVAC (V020)
IP41 on the heat-sink side with thermal separation in
push-through technique
Approvals
Types 82XX, 82XXHVAC (V020) CE: Low-Voltage Directive and
Electromagnetic Compatibility
Types 822X, 824X,
822X/4XHVAC (V020)
UL508:
UL508C:
Industrial Control Equipment
Power Conversion Equipment