Technical Data
8200SHB01993-20
3.5.4 Types 824X
120 % overload Type 8241 8242 8243 8244 8245 8246
Mains current
with mains filter/mains choke
I
mains
[A] 1.7 2.8 5.0 8.8 15.0 20.5
Data for mainsoperation with 3 AC / 400 V/ 50 Hz/60 Hz ; 460 V$ V
DC
$ 620 V
Motor power (4 pole ASM)
P
r
[kW] 0.55 1.1 2.2 4.0 7.5 11.0
at 4 kHz/8 kHz
*
P
r
[hp] 0.75 1.5 2.9 5.4 10.0 15.0
Output power U, V, W
at 4 kHz/8 kHz
*
S
r4
[kVA]
S
r8
[kVA]
1.3
1.0
2.1
1.7
3.8
2.7
6.5
4.8
11.1
9.0
16.3
16.3
Output
4kHz
*
I
r4
[A] 1.8 3.1 5.5 9.2 16.0 23.5
current
8kHz
*
I
r8
[A] 1.5 2.5 3.9 7.0 13.0 23.5
12 kHz
*
I
r12
[A] 1.35 2.2 3.5 6.3 11.7 20.0
16 kHz
*
I
r16
[A] 1.2 2.0 3.1 5.6 10.4 16.5
Noise optimised 4 kHz
*2)
I
r4
[A] 1.5 2.5 3.9 7.0 13.0 23.5
Noise optimised 8 kHz
*2)
I
r8
[A] 1.3 2.2 2.9 6.0 11.1 20.0
Noise optimised 12 kHz
*
I
r12
[A] 1.3 2.1 3.4 6.1 11.3 19.4
Noise optimised 16 kHz
*
I
r16
[A] 1.1 1.8 2.9 5.2 9.7 15.2
Max.
I
rmax4
[A] 2.25 3.6 6.6 11.0 19.5 35.3
output
8kHz
*
I
r8
[A] 2.2 3.7 5.8 10.5 19.5 35
12 kHz
*
I
r12
[A] 2.0 3.3 5.2 9.5 17.5 30.0
1)
16 kHz
*
I
r16
[A] 1.8 3.0 4.7 8.4 15.6 24.6
Noise optimised 4 kHz
*2)
I
r4
[A] 2.3 3.8 5.8 10.5 19.5 35.5
Noise optimised 8 kHz
*2)
I
r8
[A] 2.0 3.2 5.0 7.8 14.5 22.9
Noise optimised 12 kHz
*
I
r12
[A] 1.9 3.2 5.1 9.1 16.5 29.0
Noise optimised 16 kHz
*
I
r16
[A] 1.6 2.7 4.3 7.8 14.5 22.9
Power loss (operation with I
rx
) P
loss
[W] 50 65 115 165 260 360
1)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
2)
Only with variant “HVAC”
* Chopper frequency of the inverter
For more data see chapter3.4.6 and chapter 3.4.7.
Comentarios a estos manuales