Configuration
8200SHB01997-44
7.5.11.4 Setpoint input via function Motor potentiometer”
Function The setpoint input via the function ”Motor potentiometer” is only active, if C007 is set accordingly.
(Series “Standard”: see chapter 7.8, “Code table”; series“HVAC”: see chapter7.9, ”Code table”).
The fieldfrequencyischangedvia the setaccelerationand deceleration times.
Activation
Series “Standard”:
C007 = -10-, -11-, -12-, -13-, -21-:
Function
E1 E2
Setpoint = 0 Hz LOW LOW
Reduce setpoint until f
dmin
HIGH LOW
Increase setpoint untilf
dmax
LOW HIGH
Setpoint remains constant HIGH HIGH
Series HVAC: C007 = -10-, -11-, -12-, -13-, -21-, -23-, -24-, -25-, -26-, -27-, -44-:
Function E1 E2 E3
3)
E4
3)
Setpoint = 0 Hz (T
iQSP
, C105)
1)
LOW LOW LOW LOW
Reduce setpoint until f
dmin
(T
if
, C013)
2)
HIGH LOW HIGH LOW
Increase setpoint untilf
dmax
(T
ir
, C012) LOW HIGH LOW HIGH
Setpoint remains constant HIGH HIGH HIGH HIGH
1)
LOWlevel atterminalsE1 and E2 reducesthe setpoint along the QSPramp(C105)until
f
d
=0Hz
2)
Onlypossible, if the setpoint has exceeded f
dmin
before.
3)
Only, if C007 = -44-
Activation of the function Motor potentiometer” via normally-closed contacts
Series “Standard”: C007 = -10- ... -13-, -21-
Series “HVAC”: C007 = -10- ... -13-, -21- ... -27- C007 = -44-
E1 E2 E3 E4 20
^
STOP = CCW
E1 E2 E3 E4 20
^
STOP = CCW
Important The setpoint is saved
when switching off the mains,
when inhibiting the controller,
when having fault messages.
Exception:
If the control terminals are set to LOW in the event of mains failure (e.g. external voltage supply),
the setpoint 0 Hz will be stored.
Activation of the QSP function (C007 = -13-, -21-) resets the motor potentiometer to 0 Hz.
Special features The terminal configuration C007 = -13- provides an open-circuit protection for quick stop.