Configuration
8200SHB01997-32
7.5.9.4 Ramp function generator S-shape
Only “HVAC” controllers
Code Name
Possible settings
IMPORTANT
Lenze Choice Info
C182* Integration time
ramp function
generator S-shape
0.00 0.00 {0.01 s} 50.00
Function An adjustable transmission element (PT1) is connected behind the ramp function generator. The
integration time (T
i
) is set. It rounds the frequency setpoint.
This function enables absolutely smooth starting of the drive.
Adjustment C182 = 0.00
- The ramp function generator work linearly.
C182 > 0.00
- The ramp function generator works as S-shape with the time T
i
= C182.
Important C182 is only stored in parameter set 1.