Technical Data
8200SHB0199
3-19
3.5.3 Types 822X
120 % overload Type 8221 8222 8223
1)
8224 8225
1)
8226 8227
1)
Mains current
with mains filter/mains choke
I
mains
[A] 39.0 50.0 60.0 97.0 119 145 185
Data for mainsoperation with 3 AC / 400 V/ 50 Hz/60 Hz ; 460 V$ V
DC
$ 620 V
Motor power (4 pole ASM)
P
r
[kW] 22 30 37.5 55 75 90 110
at 4 kHz/8 kHz
*
P
r
[hp] 30 40 50 74 100 120 148
Output power U, V, W
at 4 kHz/8 kHz
*
S
r4
[kVA]
S
r8
[kVA]
29.8
22.2
39.5
32.6
46.4
41.6
74.8
61.7
91.5
76.2
110
103.9
142
124.7
Output
4kHz
*
I
r4
[A] 43 56 66 100 135 159 205
current
8kHz
*
I
r8
[A] 32 47 59 89 110 150 171
12 kHz
*
I
r12
[A] 27 40 50 62 88 120 126
16 kHz
*
I
r16
[A] 24 35 44 54 77 105 108
Noise optimised 4 kHz
*3)
I
r4
[A] 32 47 59 89 110 150 159
4)
Noise optimised 8 kHz
*3)
I
r8
[A] 29 43 47
4)
59
4)
76
4)
92
4)
100
4)
Noise optimised 12 kHz
*
I
r12
[A] 25 37 44 54 66 82 90
Noise optimised 16 kHz
*
I
r16
[A] 21 30 35 46 60 67 72
Max.
4kHz
*
I
rmax4
[A] 48 70.5 89 134 165 225 270
output
8kHz
*
I
rmax8
[A] 48 70.5 89 134 165 225 221
12 kHz
*
I
rmax12
[A] 40 59 75 92 114 156 164
2)
16 kHz
*
I
rmax16
[A] 36 53 66 81 100 136 140
Noise optimised 4 kHz
*3)
I
rmax4
[A] 48 70.5 89 134 165 225 238
4)
Noise optimised 8 kHz
*3)
I
rmax8
[A] 43 64 70
4)
88
4)
114
4)
138
4)
150
4)
Noise optimised 12 kHz
*
I
rmax12
[A] 38 56 66 81 85 107 117
Noise optimised 16 kHz
*
I
rmax16
[A] 31 46 53 69 78 87 94
Power loss (operation with I
r4
) P
loss
[W] 640 810 810 1350 1470 2100 2400
1)
Max. permissible ambient operating temperature + 35 C
2)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
3)
Only with variant “HVAC”
4)
Must only be operated with C144 = -1- (automatic chopper frequency derating at J
max
=+5C). Ensure not to
exceedthe currents.
* Chopper frequency of the inverter
For more data, see chapter3.4.4 andchapter 3.4.5.