Commissioning
8200SHB0199
5-15
5.4.2.4 Normalisation of an application datum
820X setting range: Function not available.
Setting range 821X/822X/824X:
Code Name
Possible settings
IMPORTANT
Lenze Choice Info
C500* Display factor
Application datum-
numerator
2000 1 {1} 25000
C501* Display factor
Application datum-
denominator
10 1 {1} 25000
Function Adaptationof field-frequencyrelatedparameters
C010, C011, C017, C019, C037, C038, C039, C046, C049, C050 and
for controllers of the “HVAC” seriesC051, C181, C625, C626, C627 additionally
to an application datum to be controlled, e.g. pressure, temperature, flow rate, humidity or speed.
The normalisation
implements an absolute or relative selection or display of an application datum,
is always carried out simultaneously for all codes indicated.
Adjustment
The display value is calculated from:
CXXX
C011
200
C500
C501
Example The speed setpoint is to be input and displayed as relative or absolute value.
Values: P
set
=5bar,iff
dmax
= 50 Hz (C011)
a) Relative normalisation in %
100.00 (%)
50
200
ô
4000
10
e.g. C500 = 4000, C501 = 10
b) Absolute normalisation in physical units
5.00 (bar)
50
200
ô
200
10
e.g. C500 = 200; C501 = 10
Important
All codesindicated above are normalisedat the same time.
After a normalisation, the output frequency[Hz](C050)can onlybe recalculated withthe display
factorsC500 and C501.