Lenze EVS9332xP Manual de usuario Pagina 78

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 334
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 77
Function library
Positioning control
3.4.8 Homing
3−50
l
EDSVS9332P−EXT DE 2.0
3.4.8.5 Homing modes 2 and 3
Purpose
l Homing in absolute positioning mode (C1210 = 0, 2), with finite traversing range and existing
travel range limit switches (POS−LIM−xxx).
l The homing switch (POS−REF−MARK) is always found. In the worst case the entire traversing
range will be searched.
Approach end of travel range limit switch, reverse and move to reference point via homing
switch
Mode 2: Traversing direction to positive end of travel range limit switch
Set C1213 = 2.
Homing switch (POS-REF-MARK)
Zero pulse / Zero position
End of
travel switch
(POS-LIM-POS)
Home position
End of
travel switch
(POS-LIM-NEG)
9300pos053
Fig. 3−17 Move to POS−LIM−POS, reverse, move to reference point via POS−REF−MARK
Function sequence
l Move to positive travel range limit switch with homing speed C1242.
l Reverse there and move beyond the reference switch to the reference point with homing
speed C1242. In this case no fault (PO2) is indicated!
l The reference point is at the first zero pulse / zero position of the position encoder after leaving
the homing switch.
l If the drive is already on the positive end of travel range limit switch before homing, it is
reversed immediately.
l If the drive is positioned at the reference switch when homing is started, the switch will be
overtravelled. The drive then goes on to the limit switch and reverses there.
Vista de pagina 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 333 334

Comentarios a estos manuales

Sin comentarios