Function library
Positioning control
3.4.3 Positioning modes (C1210)
3−31
l
EDSVS9332P−EXT DE 2.0
Position resolution
l Display via code C1205.
Display of the number of increments with which the units defined by the user are resolved
(incr/unit).
l The position resolution can be used to check for rounding errors.
Calculation example:
C1301/1 = 100.2550 units (position value in VTPOS)
C1205 = 80.0000 inc/unit (position resolution)
Formula:
Feed + C1301[units] @ C1205[incńunit]
8020, 4inc + 100, 2550units * 80, 0000incńunit
A difference of 0.4 inc results from every feed.
Tip!
If it is not possible to have increments without decimal positions, drifting of the holding position can
be avoided by touch−probe positioning.