4 The Lenze automation system with EtherCAT
4.1 Brief description of EtherCAT
20
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.1.2.1 The EtherCAT state machine
Before communication via EtherCAT is possible, the fieldbus is scanned by the EtherCAT state
machine when the installation is being powered up. The following illustration shows the possible
status changes from the point of view of an EtherCAT slave.
[4-2] EtherCAT state machine
E94AYCET009
Operational
Pre-Operational
Init
Safe-Operational
State Description
Init Initialisation phase
No SDO/PDO communication with the slaves
Device can be detected by fieldbus scan
Pre-operational The fieldbus is active.
SDO communication (mailbox communication) is possible.
No PDO communication
Safe-operational SDO communication (mailbox communication) is possible.
PDO communication:
The input data in the process image are updated.
The output data from the process image are not transferred to the slaves.
Operational Normal operation
SDO communication
PDO communication
Fieldbus synchronisation has been successful (if used)
Note!
A fieldbus scan is possible in any EtherCAT state.
Determining the physical EtherCAT configuration (fieldbus scan)
( 75)
The SDO communication via the EtherCAT bus is only possible if at least the "Pre-
Operational" state has been reached.
Only in the transitional phases between states can bus nodes be in different states.