12 Diagnostics
12.6 System error messages
184
Lenze · Controller-based Automation · EtherCAT® Communication Manual · DMS 6.4 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
0x98110015 ETC_E_UNKNOWN_MBX_PROTOCOL Unknown mailbox protocol
Mailbox command ID with unknown protocol assignment
Internal error. Please contact Lenze.
0x98110016 ETC_E_ACCESSDENIED Access denied (internal software error on the master)
Internal error. Please contact Lenze.
0x9811001A ETC_E_PRODKEY_INVALID The evaluation version of the master is used. The master enters the "Stop" mode
after 30 minutes.
Internal error. Please contact Lenze.
0x9811001B ETC_E_WRONG_FORMAT The XML file contains no or faulty content.
Internal error. Please contact Lenze.
0x9811001C ETC_E_FEATURE_DISABLED Attempt to execute a non-existing or deactivated function.
Internal error. Please contact Lenze.
0x9811001D ETC_E_SHADOW_MEMORY The shadow memory has been requested in wrong mode.
Internal error. Please contact Lenze.
0x9811001E ETC_E_BUSCONFIG_MISMATCH The EtherCAT configuration of the master and the connected slaves does not
comply with the physical bus structure.
0x9811001F ETC_E_CONFIGDATAREAD The XML file cannot be read.
Internal error. Please contact Lenze.
0x98110021 ETC_E_XML_CYCCMDS_MISSING The XML file of the master does not contain any cyclical commands.
Internal error. Please contact Lenze.
0x98110022 ETC_E_XML_ALSTATUS_READ_MISSING The XML file of the master does not contain the command for reading the AL
Status Register.
Internal error. Please contact Lenze.
0x98110023 ETC_E_MCSM_FATAL_ERROR The master state machine is in an invalid state.
Internal error. Please contact Lenze.
0x98110024 ETC_E_SLAVE_ERROR The slave cannot be addressed.
0x98110025 ETC_E_FRAME_LOST An EtherCAT frame was lost on the fieldbus, i.e. it has not been received. If this
error occurred frequently, this indicates the wiring may be faulty.
0x98110026 ETC_E_CMD_MISSING The received EtherCAT frame is not complete.
Internal error. Please contact Lenze.
0x98110028 ETC_E_INVALID_DCL_MODE This function cannot be used when DC latching is in the "Auto Read" operating
mode.
Internal error. Please contact Lenze.
0x98110029 ETC_E_AI_ADDRESS The connected slaves do not comply with the control configuration. This error
only occurs if a previously existing slave disappears.
Internal error. Please contact Lenze.
0x9811002A ETC_E_INVALID_SLAVE_STATE The mailbox commands are not permissible in the current slave state.
0x9811002B ETC_E_SLAVE_NOT_ADDRESSABLE The slave has been switched on/off.
0x9811002C ETC_E_CYC_CMDS_OVERFLOW Error during XML file creation by the configurator
Internal error. Please contact Lenze.
0x9811002D ETC_E_LINK_DISCONNECTED The EtherCAT cable has not be connected/plugged into the Lenze controller.
0x9811002E ETC_E_MASTERCORE_INACCESSIBLE The connection to the master (server) is interrupted or the master has been
stopped.
Internal error. Please contact Lenze.
0x9811002F ETC_E_COE_MBXSND_WKC_ERROR It is not possible to write to the CoE mailbox in the slave. The slave has not yet
read the mailbox.
Internal error. Please contact Lenze.
0x98110030 ETC_E_COE_MBXRCV_WKC_ERROR It is not possible to read the CoE mailbox in the slave.
Internal error. Please contact Lenze.
0x98110031 ETC_E_NO_MBX_SUPPORT The slave does not support mailbox transfer.
0x98110032 ETC_E_NO_COE_SUPPORT Configurator error or the slave description file does not correspond with the
slave firmware.
0x98110033 ETC_E_NO_EOE_SUPPORT Configurator error or the slave description file does not correspond with the
slave firmware.
0x98110034 ETC_E_NO_FOE_SUPPORT Configurator error or the slave description file does not correspond with the
slave firmware.
0x98110035 ETC_E_NO_SOE_SUPPORT Configurator error or the slave description file does not correspond with the
slave firmware.
Is not supported.
0x98110036 ETC_E_NO_VOE_SUPPORT Configurator error or the slave description file does not correspond with the
slave firmware.
Is not supported.