4×analog input
4
The modular system
4.14
L
4.14−2
EDSPM−TXXX−9.0−11/2009
AI 4x16BIT
F0
F1
F2
F3
1
2
3
4
5
6
7
8
9
L
10
EPM – T310 1B 11
0
1
epm−t029
Fig. 4.14−2 Front view 4×analog input
Status display
LED (red) is lit in case of a wire breakage in the measuring range of 4 ... 20 mA
LED (red) is blinking at an input current of >40 mA
F0 Analog input E.0
F1 Analog input E.1
F2 Analog input E.2
F3 Analog input E.3
Terminal strip
Assignment:
Two−wire connection Four−wire connection
1 Not assigned −V / analog input E.0
2 + / analog input E.0 −I / analog input E.0
3 − / analog input E.0 Not assigned
4 + / analog input E.1 +V / analog input E.0
5 − / analog input E.1 −I / analog input E.0
6 + / analog input E.2 −I / analog input E.2
7 − / analog input E.2 Not assigned
8 + / analog input E.3 +V / analog input E.2
9 − / analog input E.3 −I / analog input E.2
10 Not assigned −V / analog input E.2
Status display and terminal
assignment