32×dig. I/O compact
5
The compact system
5.4
L
5.4−3
EDSPM−TXXX−9.0−11/2009
System bus (CAN)
CANopen Baud rate
Coding switch value Coding switch value [kbit/s]
90 80 1000
91 81 500
92 82 250
93 83 125
94 84 100
95 85 50
96 86 20
97 87 10
98 88 800
Bold print = Lenze setting
1. Switch off the voltage supply of the module.
2. Use the coding switch to set the required baud rate.
Select "9x" when using the "system bus (CAN)" protocol (x = value for the
required baud rate)
Select "8x" when using the "CANopen" protocol (x = value of required
baud rate)
3. Switch on the voltage supply of the module.
The LEDs ER, RD and BA are blinking with a frequency of 1 Hz.
4. LEDs ER and BA go off after 5 seconds, and the set baud rate is stored.
5. Now set the node address with the coding switch for the module. You have
five seconds for this.
Each node address must be assigned only once.
6. The set node address will be accepted after 5 seconds.
LED RD goes off.
The module changes to the pre−operational mode.
) Note!
l The node address can be changed any time with the coding
switch. The setting is accepted after switching on the supply
voltage.
l After switching on the supply voltage, the compact system
needs approx. 1 ms for initialisation. During this time, no
parameters can be set.