16×dig. I/O compact (three−wire conductor)
5
The compact system
5.3
L
5.3−6
EDSPM−TXXX−9.0−11/2009
X5/1
X5/2
X3/10
X3/9
X3/8
X3/7
X3/6
X3/5
X3/4
X3/3
X3/2
X3/1
X5/3
X5/4
X5/5
X5/6
X5/7
X5/8
X5/9
X5/10
Z
Z
Z
Z
Z
Z
+
–
X1PE
µC
+
+
+
–
+
DC 24 V
(DC +18 … +35 V)
0
X4 X4– X6 X6–
epm−t046
Fig. 5.3−5 Wiring diagram of 16×dig. I/O compact (three−wire conductor)
Emergency−off switch
X4, X4– Terminal strips
X6, X6 Terminal strips
Z
Load
( Stop!
If the voltage supply (DC 24 V) fails, the module will malfunction:
l Switched outputs carry voltage if one input is assigned with a
HIGH level,
l The module can be destroyed since the outputs are not
resistant to short circuits anymore.
The emergency−off switch ensures that when being operated the
outputs do not carry any voltage and the inputs are not assigned
with a HIGH level.
Connection