Index table
15
Appendix
15.1
L
15.1−14
EDSPM−TXXX−9.0−11/2009
Index ImportantPossible settingsName
SelectionLenze
I4003
h
*
Set counter value
16DI/1C
0 {1} 4294967295
Module 1×counter/ 16×digital input
· Selection of the counter value
12.6−1
1 Module 1
2 Module 2
3 Module 3
... ...
8 Module 8
I4004
h
*
Control byte
16DI/1C
0 {1} 255
Module 1×counter/ 16×digital input 12.6−1
Bit
1 Module 1 0 0 Start counter
2 Module 2 0 1 Stop counter
3
Module 3 0 2 Load set counter value
...
... ... 3 Reset counter
8
Module 8 0 4 ... 7 Reserved
I4005
h
*
Fref 16DI/1C 0 {1} 255
Module 1×counter/ 16×digital input
· Selection of the reference frequency for
"Period measuring"mode
12.6−1
1 Module 1
2 Module 2
3 Module 3
... ...
8 Module 8
I4100
h
SSI counter value
00000000
h
FFFFFFFFh
Display only 12.5−1
Bit
1 Module 1 0 Control status I/O0 (LSB)
Status display only for SSI mapping PLC
(I4104
h
= 0)
2 Module 2 1 Control status I/O1
3
Module 3 2 ... 7 Reserved
4
Module 4 8 ... 15 SSI value HB
Display of current counter value of SSI
encoder
... ... 16 ... 23 SSI value MB
9
Module 9 24 ... 31 SSI value LB
I4101
h
*
SSI set counter
value
00000000
h
{1
h
} FFFFFFFF
h
12.5−1
Bit
1 Module 1 0
h
0 SSI control setpoint selection I/O0 (LSB)
Bit value 0: No selection via I/O.x
Bit value 1: Selection via I/O.x
· Settings only apply to SSI mapping PLC
mode (I4104
h
= 0)
2 Module 2 0
h
1 SSI control setpoint selection I/O1
3
Module 3 0
h
2 Reserved
4 Module 4 0
h
3 SSI control output condition 0 SSI > setpoint Bit value 0: I/O.x is set 1, if counter value >
setpoint
Bit value 1: I/O.x is set 1, if counter value <
setpoint
· Settings only apply to SSI mapping PLC
mode (I4104
h
= 0)
5 Module 5 0
h
4 ... 7 Reserved
6 Module 6 0
h
8 ... 15 SSI value HB
Setting of counter value
7 Module 7 0
h
16 ... 23 SSI value MB
8
Module 8 0
h
24 ... 31 SSI value LB
I4102
h
SSI status
Bit
Display only
· Status display only for SSI mapping
standard 1 and 2 (I4104
h
= 1 and 2)
· Current counter value of SSI encoder is
indicated under I4100
h
12.5−1
1 Module 1 0 Control status I/O0
... ... 1 Control status I/O1
9
Module 9 2 ... 7 Reserved