Parameterising 2/4xcounter module
2 × 32 bit counter with GATE and RES edge−triggered (modes 31 and 32)
13
Parameter setting via PROFIBUS−DP
13.2
13.2.16
L
13.2−44
EDSPM−TXXX−9.0−11/2009
13.2.16 2 × 32 bit counter with GATE and RES edge−triggered (modes 31 and 32)
epm−t154
Fig. 13.2−61 Terminal assignment of the 2/4xcounter in the modes 31 and 32
In the modes 31 to 32, two 32−bit counters are available, which are controlled via
a gate signal (gate). A starting value and a comparison value can be assigned to
each counter.
The modules differ in having different counting directions:
Mode 31: Upcounter.
Mode 32: Downcounter
A LOW/HIGH edge at input IN1 / IN04 (RES
û ) clears the counter.
If a HIGH level is applied to input IN3 / IN6 (GATE), the counter is incremented or
decremented by 1 with each LOW/HIGH edge.
Once the counter reaches the value loaded in the "Compare" register, output
OUT0 / OUT1 is set to HIGH level for at least 100 ms, with the counter continuing
its task.
Terminal assignment
RESû signal
GATE/CLK signal
OUT signal