Parameterising analog modules
Parameter data
13
Parameter setting via PROFIBUS−DP
13.1
13.1.1
L
13.1−3
EDSPM−TXXX−9.0−11/2009
l
For a 4×analog output module, 6 bytes of parameter data are available. The
following are defined via the parameter data
The signal function for each output (current signal output, voltage signal
output),
The module error behaviour.
l The module can be parameterised with the configuration tool or via slot and
index.
To set the parameters via slot and index, the function blocks SFB 52 (read)
and SFB 53 (write) are required.
Slot number Index Access Description
1 ... 32 00
h
R Read out diagnostic data record 0
W Write parameters to the module
01
h
R The corresponding diagnostic data record of the electronic module can be
read out via the index.
· Example:
Index 01
h
: read out diagnostic data record 1
Index 02
h
: read out diagnostic data record 2
F1
h
R Read out the module parameters
F2
h
R Read out the process image of the module
R = read
W = write
The following bytes with fixed assignment are available for parameter data:
Byte Assignment Lenze setting
0 Enabling/inhibiting diagnostic
alarm
1)
Bits 0 ...
5 %
Reserved
00
h
Bit 6
0 Alarm inhibited
12.3−6
1 Alarm enabled
Bit7
Reserved
1 Reserved
2 Selecting signal function for
output E.0
Selection of the signal function: 13.1−14
3 Selecting signal function for
output E.1
4 Selecting signal function for
output E.2
5 Selecting signal function for
output E.3
1)
The function is not available for the modules 4×analog output ±10V and 4×analog output 0...20mA.
4xanalog output modules