Lenze E94AYCEP Manual de usuario Pagina 48

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 148
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 47
8 Monitoring
8.2 Monitoring functions of the Controlled Node
49
Lenze · E94AYCEP communication module (POWERLINK MN/CN) · Communication Manual · DMS 6.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Settings
Monitoring function Description
EPL frame error (CRC) Weighted number of received faulty frames
• This error can occur due to ver strong EMC interferences or by non-
POWERLINK-compliant nodes.
• Monitoring threshold: C13131/3
/ C14131/3
• Monitoring response: C13891/4 / C14891/4
EPL-Rx PDO contents This monitoring response defines the way the cyclic process data (PDO) are
forwarded from the POWERLINKnetwork to the standard device/application
in the event of an error. An error has occurred if no valid process data is
received and the "POWERLINK synchronisation loss" monitoring function is
activated. The following settings are possible with C13885
/ C14885:
• 0: The valid data received last remains.
• 1: All data is set to the value "0".
EPL synchronisation loss This monitoring detects a failure of the Managing Node by means of the
number of POWERLINK cycles failed. This monitoring is independent of the
setting for the Drive synchronisation
( 41).
• Monitoring threshold: C13127/3
/ C14127/3
• Monitoring response: C13891/3 / C14891/3
Vista de pagina 47