PLC Designer V2.x| Lenze Application Samples
The L_SCB_CANBasic.lib library
L_SCB_CanStatus - node inspection
284 L 1.3 EN - 07/2012
17.2 L_SCB_CanStatus - node inspection
This program creates a status overview of the nodes. Incorrect nodes can be detected and
restarted.
Inputs
Note!
Only one of the two FBs (either L_SCB_CanStatus or L_SCB_StatusSingleNode)
can be used at a time!
The simultaneous use of the two FBs causes a time-out (xPDOTimeOut).
Identifier/data type Information/possible settings
tPdoTimeOut
TIME
100 ms (Lenze setting)
xAutomaticReset
BOOL
TRUE: Activate automatic restart
tResetTime
TIME
10 s (Lenze setting)
Note!
When using the visualisation template for the L_SCB_CanStatus FB, please
observe that the visualisation page does not
automatically update the status
messages.
Remedy: Click on the visualisation page or reload the visualisation window
(by switching to another window for a little while) to update the display of
the status messages.