Lenze PLC Designer V2.x Manual de usuario Pagina 278

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 336
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 277
PLC Designer V2.x| Lenze Application Samples
The L_S93_Drive9300.lib library
L_S93_ActuatorSpeed - control the 9300 Speed
278 L 1.3 EN - 07/2012
16.1.2 Structure of 93_DriveStatus_Speed - status of the controller
Further information on the interface assignments can be found in the following section:
Interface assignment in the »Global Drive Control«
( 185)
Identifier/data type Control bits in the controller
Bit Identifier Meaning
xFreeBit00
BOOL
0 Not assigned
xImp
BOOL
1DCTRL-IMP Pulse inhibit
xQSPActive
BOOL
2 STAT.B2 Activate quick stop
xDriveError
BOOL
3 STAT.B3 Status for error in the controller
TRUE: Error in the controller reported
FALSE: No error reported
xFreeBit04
BOOL
4 Not assigned
xFreeBit05
BOOL
5 Not assigned
xSpeedEqZero
BOOL
6DCTRL-NACT=0 TRUE: Speed is zero
xDriveEnabled
BOOL
7DCTRL-CINH Enable controller
xStat_1
BOOL
8 DCTRL-STAT*1 Not assigned
xStat_2
BOOL
9 DCTRL-STAT*2 Not assigned
xStat_4
BOOL
10 DCTRL_STAT*4 Not assigned
xStat_8
BOOL
11 DCTRL_STAT*8 Not assigned
xWarning
BOOL
12 DCTRL-WARN TRUE: Warning active
xMess
BOOL
13 DCTRL-MESS TRUE: Message active
xCcw
BOOL
14 STAT.B14 Not assigned
xDriveReady
BOOL
15 STAT.B15 Status signal "Controller is ready for
operation"
rNact Actual speed value
rMAct Actual torque value
rNSet Speed setpoint
Vista de pagina 277
1 2 ... 273 274 275 276 277 278 279 280 281 282 283 ... 335 336