PLC Designer V2.x| Lenze Application Samples
The L_S8V_Drive82Vector.lib library
L_S8V_ActuatorSpeed - actuation of the 8200 vector controller
268 L 1.3 EN - 07/2012
14.1.1 Actuation to the controller
The Lenze sample projects offer you a predefined mapping for the controller, in order to be
able to commission and control it. To what extent the assignments of the FB in the »PLC
Designer« are associated to the control bits in the respective device can be gathered from
the following table overview.
Further information on the controller can be found in the following
documentation:
• System manual (SHB) 8200 vector - Global Drive
–Section Function library
Code table | Controller control word (parameter
channel)
Identifier/data type Control bits in the controller
Bit Identifier Meaning
xJog1
BOOL
0NSET1-JOG1 Setpoint selection 1
xJog2
BOOL
1NSET1-JOG2 Setpoint selection 2
xCcw
BOOL
2 DCTRL1-CW/CCW Activate CCW rotation
xQSP
BOOL
3DCTRL1-QSP Activate quick stop
xNSet_RfgStop
REAL
4 NSET1-RFG1-STOP Stop ramp function generator
xNSet_Rfg0 5NSET1-RFG1-0 Ramp function generator input = 0
• RFG1 = ramp function generator of main
setpoint
xMPOT_UP 6MPOT1-UP UP function of motor potentiometer
xMPOT_DOWN 7MPOT1-DOWN DOWN function of motor potentiometer
xFreeBit08
BOOL
8 Reserved
xEnable
BOOL
9DCTRL1-CINH 1 = Enable controller (RFR)
xErrorSet
BOOL
10 DCTRL1-TRIP-SET 1 = set error (TRIP set)
xErrorReset
BOOL
11 DCTRL1-TRIP-RESET 1 = reset error (TRIP reset)
xFreeBit12
BOOL
12 Not assigned
xFreeBit13
BOOL
13 Not assigned
xFreeBit14
BOOL
14 Not assigned
xFreeBit15
BOOL
15 Not assigned
rNSet
REAL
Speed setpoint