L-force | PLC Designer
What is What in PLC Designer
58 DMS 3.2 EN 02/2011 TD29
When <Instructions> are executed, <INT_Var> is always increased by <Step size>. The
step size can have any integer value. If it is missing, then it is set to 1. The loop must
also end since <INT_Var> only becomes greater.
Example:
FOR Counter:=1 TO 5 BY 1 DO
Var1:=Var1*2;
END_FOR;
Erg:=Var1;
Let us assume that the default setting for Var1 is the value 1. Then it will have the
value 32 after the FOR loop.
Note!
<END_VALUE> must not be equal to the limit value of the counter <INT_VAR>. For
example: If the variable Counter is of type SINT and if <END_VALUE> is 127, you will
get an endless loop.
WHILE loop
The WHILE loop can be used like the FOR loop with the difference that the break-off
condition can be any Boolean expression. This means you indicate a condition which,
when it is fulfilled, the loop will be executed.
Syntax:
WHILE <Boolean expression>
<Instructions>
END_WHILE;
The <Instructions> are repeatedly executed as long as the <Boolean_expression>
returns TRUE. If the <Boolean_expression> is already FALSE at the first evaluation,
then the <Instructions> are never executed. If <Boolean_expression> never assumes
the value FALSE, then the <Instructions> are repeated endlessly which causes a
relative time delay.