L-force | PLC Designer
Lenze specifications
24 DMS 3.2 EN 02/2011 TD29
2.1.2 Updating the Lenze target "V5 Logic with Motion" to "V6 Logic with Motion"
Step V5 Logic with Motion-> V6 Logic V5 Logic with Motion- > V6 Logic with Motion
1 Do not convert, as Motion components are lost
during conversion to the Logic target!
Open org. V5 project
2
Set "Save configuration files in project“
option
3
Save project
4
Select the V6 target under Target system
settings Ω Configuration
5
Add the following function libraries in the
Library manager to the project:
3S_CANOpenMaster.lib
SM_CANWatch.lib
SM_CAN.lib und
LenzeCANdrive.lib
6
Remove
the\Motion\Drives\CAN\3S_CanDrv.lib
function library from the project in the Library
manager
7
Add the 3S_CanDrv.lib function library to the
project in the Library manager
8
Save and close project
9
Open project
10
Translate project completely
Possibly incompatibilities are caused by new
lib versions which then have to be
individually edited manually.
Example: In contrast to the version from the
V5 target, the SMC_Interpolator FB from the
V6 target has two basic inputs.
2.1.3 Updating the Lenze target "V6 Logic" to "V6 Logic with Motion"
Step V6 Logic -> V6 Logic with Motion
1 Open org. V6 Logic project
2
Select the V6 Logic + Motion Target under Target system settings Ω Configuration
3 Translate project completely