8.5 System error messages
Drive PLC
Appendix
8−10
L
DrivePLC DE 6.0
System error message Possible settings/response
Lenze setting ü setting possible
Available in
No. Display Source Meaning
Code TRIP Message Warning FAIL−
QSP
Off Drive
PLC
Servo
PLC
ECSxA
Floating−point error (REAL) in:
x209 FLOAT SYS−T
internal
System task
2)
ü ü ü ü ü
x210 FLOAT CYCL.−T Cyclic task (PLC_PRG, ID 1)
x211 float T Id2 Task with ID 2
x212 float T Id3 Task with ID 3
x213 float T Id4 Task with ID 4
x214 float T Id5 Task with ID 5
x215 float T Id6 Task with ID 6
x216 float T Id7 Task with ID 7
x217 float T Id8 Task with ID 8
x218 float T Id9 Task with ID 9
x220 NoT−FktCredit internal Not enough technology units available in the
PLC
ü ü ü
x230 No Program internal No PLC program loaded in PLC ü ü ü
x231 Unallowed Lib internal A library function has been called in the PLC
program which is not supported
ü ü ü
x232 NoCamData internal Motion profiles (cam data) are not available ü ü ü
Free CAN objects:
x240 ovrTransQueue
Free CAN
obj.
Overflow of send order memory C0608 ü ü ü
3)
ü ü ü ü
x241 ovr Receive Too many receive telegrams C0609 ü ü ü
Application memory (FLASH):
x250 2.Flash Err internal Access not possible
1)
(FLASH memory defective or not available)
ü
x251 AddData CsErr internal Check sum error occurred when loading data
into the FLASH memory
x252 AddData DlErr internal Error occurred when downloading data into the
FLASH memory (e.g. time−out)
x260 Err NodeGuard Node
guarding
"Life guarding event": The PLC as a CAN slave
has not received any "node guarding" telegram
within the node lifetime of the CAN master.
C0384 ü ü ü
3)
ü ü ü ü
x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP
1)
After error correction: completely deenergise the device!
2)
In DDS adjustable under Project W Exception response
3)
Only with 9300 Servo PLC!