2.7 ANALOG2_IO (node number 12)
Drive PLC
System blocks
2−22
L
DrivePLC DE 6.0
2.7 ANALOG2_IO (node number 12)
2.7.1 Inputs_ANALOG2 (analog input)
This SB forms the interface for analog signals via terminal AI2, A.
AI2
A
AIN2_nIn_a
Inputs_ANALOG2
C0400/2
Fig. 2−12 Inputs_ANALOG2
System variables
Variable Data type Signal type Address Display
code
Display
format
Notes
AIN2_nIn_a Integer analog %IW12.0 C0400/2 dec [%] Analog input 2
Terminal assignment
Terminal Use Data
AI2 Analog input 2 Level:
Resolution:
Internal resistance:
Normalisation:
−10 V ... +10 V
10 bits + sign
100 k
10 V 16384 100 %
A Internal ground, GND −