7.1 ANALOG4_IO_EB3 (node number 14)
Drive PLC
System blocks − Extension Board 3
7−2
L
DrivePLC DE 6.0
7.1 ANALOG4_IO_EB3 (node number 14)
7.1.1 Inputs_ANALOG4 (analog input 4 of extension board 3)
This SB is the interface for analog signals via terminal AI4, A of the extension board 3.
AI4
A
AIN4_nIn_a
Inputs_ANALOG4
Fig. 7−1 Inputs_ANALOG4
System variables
Variable Data type Signal type Address Display
code
Display
format
Notes
AIN4_nIn_a Integer analog %IW14.0 − dec [%] Analog input 4
Terminal assignment
Terminal X2 Use Data
AI4 Analog input 4 Level:
Resolution:
Internal resistance:
Normalisation:
−10 V ... +10 V
10 bits + sign
100 k
10 V 16384 100 %
A Internal ground, GND −