3.1 ANALOG_IO_FIF (node number 201)
Drive PLC
System blocks − FIF Standard−I/O
3−2
L
DrivePLC DE 6.0
3.1 ANALOG_IO_FIF (node number 201)
3.1.1 Inputs_ANALOG_FIF (analog input, "Standard I/O" FIF module)
This SB forms the interface for analog signals via terminal 8 of the Standard I/O FIF module as
setpoint input or actual value input.
8
AIN1_nIn_FIFSTDIO_a
Inputs_ANALOG_FIF
C0481
A
D
7
Fig. 3−1 Inputs_ANALOG_FIF
System variables
Variable Data type Signal type Address Display
code
Display
format
Notes
AIN1_nIn_FIFSTDIO_a Integer analog %IW201.0 C0481 dec [%] Analog input 1
Standard I/O
Input signal setting
By suitable switch settings at the Standard I/O FIF module the following input signals can be
processed:
Input range
1)
for terminal 8
Switch setting
1 2 3 4 5
0 ... +5 V OFF OFF ON OFF OFF
0 ... +10 V (Lenze setting) OFF OFF ON OFF ON
−10 ... +10 V ON ON OFF OFF OFF
0 ... +20 mA OFF OFF ON ON OFF
1)
The selected input range is adjusted to the integer range (0 ... 16384) of the variable AIN1_nIn_FIFSTDIO_a.
Example: selected input range = 0 ... +10 V
Input signal (terminal 8) 0 V + 5 V + 10 V
AIN1_nIn_FIFSTDIO_a 0 8192 16384
Electrical data of the input terminals:
Terminal Use level Data
8 Analog input 1 0 ... +5 V
0 ... +10 V
−10 ... +10 V
0 ... +20 mA
Resolution:
Linearity error:
Temperature error:
Input resistance:
10 bit
0.5 %
0.3 % (0 ... 60 °C)
> 50 k (voltage signal)
250 (current signal)
7 GND1, reference potential
for analog signals
− −
Tip!
Detailed information about the terminal assignment for the Standard I/O FIF module can be found
in the corresponding Mounting Instructions!