2.6 ANALOG1_IO (node number 11)
Drive PLC
System blocks
2−20
L
DrivePLC DE 6.0
2.6 ANALOG1_IO (node number 11)
2.6.1 Inputs_ANALOG1 (analog input)
This SB forms the interface for analog signals via terminal AI1, A as setpoint input or actual value
input.
AI1
A
AIN1_nIn_a
Inputs_ANALOG1
C0400/1
Fig. 2−10 Inputs_ANALOG1
System variables
Variable Data type Signal type Address Display
code
Display
format
Notes
AIN1_nIn_a Integer analog %IW11.0 C0400/1 dec [%] Analog input 1
Terminal assignment
Terminal Use Data
AI1 Analog input 1 Level:
Resolution:
Internal resistance:
Normalisation:
−10 V ... +10 V
10 bits + sign
100 k
10 V 16384 100 %
A Internal ground, GND