Drive PLC
Appendix
8.6 Code table
8−29
L
DrivePLC DE 6.0
Code InfoPossible settingsLCDCode Info
SelectionLenze
LCD
C0868 DIS: OUTx.Wx
g
System bus: Process data output words
−32768 {1 %} 32767
1 CAN1_nOutW1_a
2 CAN1_nOutW2_a
3 CAN1_nOutW3_a
4 CAN2_nOutW1_a
5 CAN2_nOutW2_a
6 CAN2_nOutW3_a
7 CAN2_nOutW4_a
8 CAN3_nOutW1_a
9 CAN3_nOutW2_a
10 CAN3_nOutW3_a
11 CAN3_nOutW4_a
C1120 Sync mode 0 System bus: Sync source
0 Off
1 Synchronisation via system bus (CAN)
2 Synchronisation via terminal X3/I1
C1121 Sync cycle 2 System bus: Synchronisation cycle
Definition of the cycle time of the sync telegram/signal.
Parameterisation is only required for the slave!
1 {1 ms} 13
C1122 Sync phase 0 System bus: Synchronisation phase
Phase shift between the sync telegram/signal and the
start of the internal control program.
0 {0.001 ms} 6.5
C1123 Sync window 0 System bus: Synchronisation window
If the sync telegram/signal sent from the master is
within the "time window",
CAN_bSyncInsideWindow_b = TRUE.
0 {0.001 ms} 6.5
C1810 S/W Id keypad
g
Keypad identification
C1811 S/W date keypad
g
Keypad creation date
C2100 Time slice 13 Time slice for task switch between system task and cyclic
task (PLC_PRG)
6 {1 ms} 26
C2102 Task switch 0 Configuration of task switch process
Activation after:
0 Time slice
1 Time slice + end PLC_PRG
2 Time slice + end PLC_PRG + end system task
C2104 PLC Autorun 0 Automatic start of the PLC program after power switch−on
0 No auto start
1 Auto start after mains connection
C2106 Downl.protect 0 Write protection for the PLC program
0 New download possible
1 No new download possible
C2107 PwDownlProt. 0 Password for download write protection (C2106)
0 {1} 4294967295
C2108 PLC run/stop 0 PLC program
0 No function
1 PLC run
2 PLC stop
3 PLC reset
start
stop
reset
C2110 Internal code