Data transfer
DRIVECOM profile parameters
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.7
L
7.6-46
EDSIBS-1.0-06/2003
This parameter is for the deceleration of the relative speed ramp. The deceleration
time refers to the parameter Speed reference value.
Ramp gradient:
Gradient =
Speed reference value (604E
hex
)
Deceleration time (6050
hex
)
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
ramp-min-function.Ifthedeceleration time = 0, the ramp is switched off.
Parameter name (Index) Subindex Data structure Data typ e Value range
Deceleration time (6050
hex
) 0 S U32 0 to 495000 [ms]
(max. L-C0013 / 2)
This parameter is assigned to the relative speed ramp for the unit-control
commands quick stop and CTRL inhibit or the QSP terminal function. The
quick stop time refers to the parameter Speed reference value.
Ramp gradient:
Gradient =
Speed reference value (604E
hex
)
Quich stop time (6051
hex
)
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
ramp-min-function.Ifthequick stop time = 0, the ramp is switched off.
Parameter name (Index) Subindex Data structure Data typ e Value range
Quick-stop time (6051
hex
) 0 S U32 0 to 495000 [ms]
(max. L-C0105 / 2)
Deceleration time (6050
hex
)
Quick-stop time (6051
hex
)