Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-8
EDSIBS-1.0-06/2003
Device status word AIF-STAT for 82XX (Lenze code C0150, index 5F69
hex
)
Bit 820X 821x, 822x
0 Actual parameter set 0=Parameterset1or3active
1=Parameterset2or4active
Actual parameter set 0=Parameterset1or3active
1=Parameterset2or4active
1 IMP (pulse inhibit) 0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
IMP (pulse inhibit) 0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
2 I
max
(current limit reached) 0 = Current limit not reached
1 = Current limit reached
I
max
(current limit reached) 0 = Current limit not reached
1 = Current limit reached
3 not assigned f
d
=f
dset
0=f
d
f
dset
1=f
d
=f
dset
4 f
d
=f
dset
0=f
d
f
dset
1=f
d
=f
dset
RFG on = RFG off 0=RFGon RFG off
1 = RFG on = RFG out
5 Qmin (f
d
f
dQmin
) 0 = Qmin not active
1=Qminactive
Qmin (f
d
f
dQmin
) 0 = Qmin not active
1=Qminactive
6 f
d
+ 0 (act. frequency = 0) 0=f
d
0
1=f
d
+0
f
d
+ 0 (act. frequency = 0) 0=f
d
0
1=f
d
+0
7 Ctrl. inhibit (controller inhibit) 0 = Controller not inhibited
1 = Controller inhibited
Ctrl. inhibit (controller inhibit) 0 = Controller not inhibited
1 = Controller inhibited
8...11 Controller status 0 = Unit initialisation
8=Erroractive
Controller status 0 = Controller initialization
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error a ctive
12 Overtemperature warning 0=Nowarning
1=Warning
Overtemperature warning 0=Nowarning
1=Warning
13 V
Gmax
(DC-bus overvoltage) 0 = No overvoltage
1 = Overvoltage
V
Gmax
(DC-bus overvoltage) 0 = No overvoltage
1 = Overvoltage
14 Direction of rotation 0 = CW rotation
1 = CCW rotation
Direction of rotation 0 = CW rotation
1 = CCW rotation
15 Ready for operation 0 = Not ready for operation
1 = Ready f or operation
Ready for operation 0 = Not ready for operation
1 = Ready f or operation
16 bits
16 bits
.B15
.B12
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B13
.B14
.B5
.B6
.B7
IMP
fd=fdset / RFG
Qmin
Imax
- / fd=fdset
PAR
fd>0
ctrl. inhibit
Vgmax
R/L
RDY
T
ü
AIF
C0050
STAT
B11 B10 B9 B8
0
0
1
.
.
.
.
.
.
0
1
1
.
.
.
.
.
.
0
0
0
.
.
.
.
.
.
0
0
0
.
.
.
.
.
.
0
2
3
.
.
.
.
.
.
2141LON012_en
Fig. 7.6-1 Read access to status word and actual frequency in 82XX (fixed assignment)