Commissioning
Possible settings with INTERBUS master
7
Feldbus-Baugruppe 2113 INTERBUS
7.5
7.5.3
L
7.5-4
EDSIBS-1.0-06/2003
7.5.3 Possible settings with INTERBUS master
)
))
) Note!
Conditions for setting through the INTERBUS master:
Switch S1 ... S7 = OFF
l The configurations set for the codes L-1910, L-1911 and
L-1912
get active with switching on.
l The settings can be changed.
l Switch off the voltage supply of the fieldbus module and
afterwards on again, in order to activate changed settings.
As a maximum the data word sum (PD + PCP) is to amount to 10
words.
Index detection: 24575 - Lenze code number (L-C xxxx )
Impermissible settings are indicated by the yellow bus LED
(communication)
(¶ 7.4-1).
Code Values Explanation
L-C1910 2 ... 20 (1 ... 10 words) Number of process data bytes
(2 Process data bytes = 1 Process data word)
L-C1911
0: Device control AIF-CTRL
Operation with device control AIF-CTRL or
1: DRIVECOM control
operation with DRIVECOM-Profil 21
L-C1912
Number of parameter
data words (PCP)
ID code
Number of parameter data words (PCP)
0 3
hex
1 E3
hex
2 E0
hex
4 E1
hex
Code Explanation
L-C1915 Display of the current switch positions S1 ... S4 for number of process data words
-
sp
ay o
t
e current pos
t
on o
sw
tc
7.
-
-
.
Display codes