Vista de pagina 62
Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-12
EDSIBS-1.0-06/2003
Controller status word AIF-STAT for 8200 vector (Lenze code C0150, index 5F69
hex
)
AIF-STAT.Bxx Lenze setting Adjustab le in code L-0417/..
0 DCTRL-PAR-B0 1
1 DCTRL1-IMP 2
2 MCTRL1-IMAX 3
3 MCTRL1-RFG1=NOUT 4
4 NSET1-RFG1-I=0 5
5 PCTRL1-QMIN 6
6 DCTRL1-NOUT=0 7
7 DCTRL1-CINH 8
8...11 Controller status
0 = Controller initialization
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error a ctive
Reserved
12 DCTRL1-OH-WARN 13
13 DCTRL1-OV 14
14 DCTRL1-CCW 15
15 DCTRL1-RDY 16
AIF-OUT
AIF-STAT
16 bits
16 bits
.B15
.B12
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
16 bits
.B13
.B14
.B5
.B6
.B7
.B0
C0417/1
AIF-OUT.W1
AIF-OUT.W2
.B1
DCTRL1-IMP
.B2
C0417/3
.B3
C0417/4
.B4
C0417/5
.B5
C0417/6
.B6
DCTRL1-NOUT=0
.B7
DCTRL1-CINH
.B8
DCTRL1-STAT*1
.B9
DCTRL1-STAT*2
.B10
.B11
DCTRL1-STAT*4
DCTRL1-STAT*8
.B12
DCTRL1-OH-WARN
.B13
DCTRL1-OV
.B14
C0417/15
.B15
C0417/16
AIF
STAT1
C0421/1
C0421/2
2141LON013_en
Fig. 7.6-3 Function block AIF-OUT in 8200 vector (freely programmable assignment)