Commissioning
Possible settings with the front switch
7
Feldbus-Baugruppe 2113 INTERBUS
7.5
7.5.2
L
7.5-2
EDSIBS-1.0-06/2003
7.5.2 Possible settings with the front switch
)
))
) Note!
Switches S1 ... S7
l All in OFF position:
The configurations set for the codes L-1910, L-1911
and
L-1912
get active with switching on.
l One or several switches in ON position:
All switch positions are valid!
The following must be set:
– Number of process data words (PD),
– Number of parameter data words (PCP) and
– Device control AIF-CTRL / DRIVECOM control
The Lenze setting of the switches (S1 - S8) is OFF .
Switch off the voltage supply of the fieldbus module and
afterwards on again, in order to activate changed settings.
As a maximum the data word sum (PD + PCP) is to amount to 10
words.
Please note that only the switch combinations listed in the
following tables represent defined
states. If the settings are
unacceptable, the yellow bus LED at the front of the fieldbus
module will start blinking (8kHz).
ON
OFF
OPEN
12345678
Length
PD
2113IBU005
PD S1 S2 S3 S4 Maximum number of
parameter data words
(PCP)
1 OFF OFF OFF ON
2 OFF OFF ON OFF
3 OFF OFF ON ON
4 OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8 ON OFF OFF OFF
9 ON OFF OFF ON 1
10 ON OFF ON OFF 0
)
))
) Note!
Impermissible settings are indicated by the yellow bus LED
(communic ation).
(¶ 7.4-1) .
Display of the current switch position S1 ... S4 for number of
process data words (PD) is possible because of code L-C1915.
Setting number of process data
words (PD)30