Lenze CANopen control technology Manual de usuario Pagina 34

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 105
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 33
Control technology | CANopen communication manual
Planning the CANopen network
Device specifications of the field devices
34 L DMS 4.2 EN 07/2011 TD17
6.2.5 Special features of the 8200 vector frequency inverter
Basic identifier - 8200 vector with fieldbus function module CANopen E82ZAFUC0xx
The default setting of the basic identifier is as follows:
1) When creating the sync transmit/receive identifier manually, observe the use of the emergency telegram because of
the same COB-ID.
Object Direction Basic identifier
from the drive to the drive dec hex
NMT 0 0
Sync 1) 128 80
Emergency z 128 80
PDO1
(process data channel 1)
TPDO1
z 384 180
RPDO1
z 512 200
PDO2
(process data channel 2)
TPDO2
z 640 280
RPDO2
z 768 300
PDO3
(process data channel 3)
TPDO3
z 896 380
RPDO3
z 1024 400
SDO1
(parameter data channel 1)
TSDO1
z 1408 580
RSDO1
z 1536 600
SDO2
(parameter data channel 2)
TSDO2
z 1472 5C0
RSDO2
z 1600 640
Node guarding z 1792 700
Vista de pagina 33