Configuration
Basic configurations
2.2.4 Master frequency coupling
2−22
l
EDSVS9332S−EXT EN 2.0
Features
The features describe the basic properties of this configuration. Some of them, however, can only
be used by reprogramming.
l Resolver feedback is possible only
l Evaluation of the setpoint (cascading factor) is possible with a factor (numerator/denominator)
for the master frequency output (and thus for all following drives)
l Other evaluation of the setpoint is possible with a factor (numerator/denominator) for the
corresponding slave (gearbox adaptation). Can be set via an analog signal source (standard:
code C0032, C0033)
l External torque limitation is possible
l The QSP or CINH function in the individual drive do not influence the setpoint for the cascade.
l Possible interventions for phase trimming and speed correction via
LECOM,
analog terminal or
one of the signal sources (function blocks).
l Message "following error limit reached" can be set via code
l TRIP when reaching the phase controller limit
l Speed limit of slave 0 = C0011
l Phase controller influence can be set and switched off via the digital input
l Homing function is possible via zero track or touch probe
l Synchronising to a setpoint is possible via zero track or touch probe
l Synchronising characteristic can be set via ramp−function generator