Function library
Function blocks
3.2.17 Signal conversion (CONV)
3−48
l
EDSVS9332S−EXT EN 2.0
CONV3
CONV3
CONV3-OUT
CONV3-IN
C0953
C0952
C0950
C0951
Fig. 3−44 Function block CONV3
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
CONV3−IN phd C0953 dec [rpm] C0952 4 1000
CONV3−OUT a Limited to ±199.99 %
This function block is used to convert speed signals into analog signals.
The conversion is done according to the formula:
CONV3−OUT + CONV3−IN @
100%
15000 rpm
@
C0950
C0951
CONV4
CONV4
CONV4-OUT
CONV4-IN
C0958
C0957
C0955
C0956
Fig. 3−45 Function block CONV4
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
CONV4−IN phd C0958 dec [rpm] C0957 4 1000
CONV4−OUT a Limited to ±199.99 %
This function block is used to convert speed signals into analog signals.
The conversion is done according to the formula:
CONV4−OUT + CONV4−IN @
100%
15000 rpm
@
C0955
C0956
CONV5
CONV5
CONV5-OUT
CONV5-IN
C0658
C0657
C0655
C0656
Fig. 3−46 Function block CONV5
Signal
Source Note
Name Type DIS DIS format CFG List Lenze
CONV5−IN a C0658 dec [%] C0657 1 1000
CONV5−OUT phd Limited to ±29999 rpm
This function block is used to convert analog signals into speed signals.
Conversion according to formula:
CONV5−OUT + CONV5−IN @
15000 rpm
100%
@
C0655
C0656
Vista de pagina 99